Leading Manufacturer of Audio & Video System

Contact US
Tel: +86-20-84593197
Email: info@itc-pa.com.cn

www.facebook.com/gzitc www.linkedin.com/in/simonitc twitter.com/GuangzhouITC google.com/+ItcpaCnSimon www.youtube.com/channel/UC67wNxwMTP3SLGeCrKaHf7w
Home  >  Products  >  EVAC System  >  Fire Alarm Equipment  >  VA-6200MS
  • EVAC Spare Amplifier Controller
  • VA-6200MS

Front and Rear Panel

Descriptions

* Built-in 500W amplifier, with 8 zones and A+B independent dual speaker loop output, each zone has independent LED indicator light, output control button and volume adjustment.

* Audio processing with 6 general audio inputs,  it can connect with external microphone, CD player, tuner and etc, it can play any audio source in any zone.

* Connecting with one piece of backup amplifier, when built-in amplifier damaged, it will switch to backup amplifier automatically.

* Automatically monitor every zone speaker loop status in real-time

* There are 8 channels trigger input/output ports, which can trigger the pre-edited voice message to the specified zones or (trigger) the relative external power supply to realize early warning for the relative incident.   

* Extension port can connect controller and next extension device.

Specifications

Model

VA-6200MS

Rated Power Output

500W

Output Voltage

100V

MIC1-2 Input Distortion

1% (output rating), 1KHz

MIC1-2 Input Frequency Response

80Hz~20KHz

MIC1-2 Input Sensitivity

5mV/6/600Ω

MIC1-2 Input SNR

>65dB

AUX3-6 Input Distortion

1% (output rating), 1KHz

AUX3-6 Input Frequency Response

80Hz~20KHz

AUX3-6 Input Sensitivity

350mV/10kΩ

AUX3-6 Input SNR

>70dB

Spare Amplifier Input

100V

Spare Amplifier Audio Signal Output

1V

Alarm Input 

8

Alarm Output

8

Zone Input

8

24V Relay Output

8

Short Circuit mode

No voltage short circuit

Type of cooling

air-cooled

Guard mode

delay/overheat/ short circuit/ overload

output Volume Control

6

Supply Voltage

~ 230V, 50/60Hz

Maximum Current

3A

Fuse Size

250V/5A, slow type

Spare Voltage

24V DC, ±20%

Maximum Current

25A

Maximum Power Consumption

600W

Dimensions (L×W×D)

484×88×353mm

Weight

10.5kg

Diagram


Connectors

1   Power switch

2   AC power outlet

3   DC 24V input interface

4   Fire alarm trigger output node

5   Fire alarm trigger input node

6   3 wire power amplifier 100V output

7   485 Online interface

8   DC 24V output

9   Unplug code switch from computer address

10   Backup power amplifier 100V input

11   Backup power amplifier signal output

12   SYS CONTRCL: 

    1) System fault output, When something goes wrong, This port will be closed

    2) Fire alarm output, When the fire alarm is triggered, This port will be closed

    3) Emergency reset input, Short circuit interface, Fire alarm will be reset

13   Impedance correction button

14   6 way background music input



Connectors

1   Power switch

2   AC power outlet

3   DC 24V input interface

4   Fire alarm trigger output node

5   Fire alarm trigger input node

6   3 wire power amplifier 100V output

7   485 Online interface

8   DC 24V output

9   Unplug code switch from computer address

10   Backup power amplifier 100V input

11   Backup power amplifier signal output

12   SYS CONTRCL: 

    1) System fault output, When something goes wrong, This port will be closed

    2) Fire alarm output, When the fire alarm is triggered, This port will be closed

    3) Emergency reset input, Short circuit interface, Fire alarm will be reset

13   Impedance correction button

14   6 way background music input


Specification

3d product demo